JBE-2200
Envío 3-4 díasMódulo analógico
Módulo de entrada convencional
Alimentación por lazo o externa
Cable conductor hasta 2.5mm2
REOL de 4k7 Ω (suministrada)
Certificado EN 54-18
1 Input / 1 Output analog module. Designed, manufactured and certified according to standard EN54-18. Each module provides an output to the fire detection system and a confirmation input. Designed to control external equipment that needs to be activated, such as fire doors, gates, elevator shutdown, etc. It can be linked to any point in the system. The confirmation input can be used to supervise, from the panel, the electrical confirmation signal that follows the activation of the output (limit switch or any other signal). The output can be configured as a voltage-free dry relay or as a 24V supervised output. In order to provide an active (24V) output, the module must be externally powered at 24V. Dimensions: 85 x 85 x 41 mm.